91
Learning Basic Features
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
minimum voltage
(%)
0.00%
14
V1 maximum input
voltage
V1- Volt x2
-10.00
-12.00 –0.00
V
V
15
V1 output at
maximum voltage
(%)
V1- Perc y2
-100.00
-100.00
0.00%
%
Rotational Directions for Different Voltage Inputs
Command /
Voltage Input
Input voltage
0–10 V
-100 V
FWD
Forward
Reverse
REV
Reverse
Forward
-10–10 V Voltage Input Setting Details
Code
Description
IN-12 V1- volt
x1
IN-15 V1- Perc
y2
Sets the gradient level and off-set value of the output frequency in relation
to the input voltage. These codes are displayed only when IN-06 is set to 1
(bipolar)‘.
As an example, if the minimum input voltage (at V1) is set to -2 (V) with
10% output ratio, and the maximum voltage is set to -8 (V) with 80% output
ratio respectively, the output frequency will vary within the range of 6–48
Hz.