EasyManua.ls Logo

LSIS LSLV0055H100-4COFN - Setting a Frequency Reference with Input Voltage (Terminal I2)

LSIS LSLV0055H100-4COFN
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
95
Learning Basic Features
4.2.4 Setting a Frequency Reference with Input Voltage (Terminal
I2)
Set and modify a frequency reference using input voltage at I2 (V2) terminal by setting SW2
to V2. Set the DRV-07 (Frequency reference source) to 4 (V2) and apply 0–12 V input
voltage to I2 (=V2, Analog current/voltage input terminal). Codes IN-3547 will not be
displayed when I2 is set to receive current input (DRV-07 is set to5‘).
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
DRV
07
Frequency
reference source
Freq Ref
Src
4
V2
011
-
IN
35
V2 input display
V2 Monitor
0.00
0.00–12.00
V
37
V2 input filter time
constant
V2 Filter
10
010000
msec
38
Minimum V2 input
voltage
V2 Volt x1
0.00
0.00–10.00
V
39
Output% at
minimum V2
voltage
V2 Perc y1
0.00
0.00–100.00
%
40
Maximum V2 input
voltage
V2 Volt x2
10.00
0.00–10.00
V
41
Output% at
maximum V2
voltage
V2 Perc y2
100.00
0.00–100.00
%
46
Invert V2 rotational
direction
V2 Inverting
0
No
0–1
-
47
V2 quantizing level
V2
Quantizing
0.04
0.00*, 0.04
10.00
%
* Quantizing is disabled if 0‘ is selected.

Table of Contents