Learning Basic Features
96
4.2.5 Setting a Frequency with TI Pulse Input
Set a frequency reference by setting the Frq (Frequency reference source) code (code 07)
in DRV group to 9 (Pulse) and provide 0–32.00 kHz pulse frequency to TI terminal.
Grou
p
Cod
e
Name
LCD Display
Parameter Setting
Setting
Range
Unit
DRV
07
Frequency reference
source
Freq Ref
Src
9
Pulse
011
-
IN
01
Frequency at
maximum analog
input
Freq at
100%
60.00
0.00
Maximum
frequency
Hz
91
Pulse input display
TI Monitor
0.00
0.00–50.00
kHz
92
TI input filter time
constant
TI Filter
10
09999
mse
c
93
TI input minimum
pulse
TI Pls x1
0.00
0.00–32.00
kHz
94
Output% at TI
minimum pulse
TI Perc y1
0.00
0.00–100.00
%
95
TI Input maximum
pulse
TI Pls x2
32.00
0.00–32.00
kHz
96
Output% at TI
maximum pulse
TI Perc y2
100.00
0.00–100.00
%
97
Invert TI direction of
rotation
TI Inverting
0
No
0–1
-
98
TI quantizing level
TI
Quantizing
0.04
0.00*, 0.04
10.00
%
*Quantizing is disabled if 0 is selected.

Table of Contents