EasyManua.ls Logo

LSIS LSLV0055H100-4COFN - Command Source Configuration; The Keypad as a Command Input Device

LSIS LSLV0055H100-4COFN
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Learning Basic Features
102
4.6 Command Source Configuration
Various devices can be selected as command input devices for the H100 inverter. Input
devices available to select include keypad, multi-function input terminal, RS-485
communication and field bus adapter.
Grou
p
Cod
e
Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV
06
Command
Source
Cmd
Source
0
Keypad
0–5
-
1
Fx/Rx-1
2
Fx/Rx-2
3
Int 485
4
Field Bus
5
Time Event
4.6.1 The Keypad as a Command Input Device
To use the keypad as the command source, press the [AUTO] key to enter AUTO mode.
Set DRV-06 to0 (Keypad)‘ to select the keypad as the command source and set the
operation direction at DRV-02 (Keypad Run Dir).
Since the keypad is now the command source, operation starts when the AUTO key is
pressed, and it stops when the AUTO key is pressed again.
The OFF key may be used to stop the operation as well, but the inverter operation mode
will be changed to OFF mode.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV
06
Command
source
Cmd Source
0
KeyPad
0–5
-

Table of Contents