Learning Advanced Features
Anti-hunting Regulation Setting Details
Code
Description
CON-13 AHR Sel
Selects the Anti-hunting regulator operation.
Setting
Function
0
No
Disable anti-hunting regulation.
1
Yes
Enable anti-hunting regulation.
CON-14 AHR P-Gain
Increasing AHR proportional gain improves responsiveness of the
anti-hunting regulation. However, current oscillation may result if
AHR proportional gain is set too high.
CON-15 AHR Low Freq
CON-16 AHR High
Freq
Sets the lower limit frequency (CON-15) and the maxim limit
frequency (CON-16) for anti-hunting regulation.
5.25 Fire Mode Operation
This function is used to allow the inverter to ignore minor faults during emergency situations,
such as fire, and provides continuous operation to protect other systems, such as
ventilating fans. In Fire mode, the inverter continues to operate based on the Fire mode run
direction and frequency set at PRT-46 and PRT-47.
Grou
p
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
PRT
44
Fire mode
password
Fire Mode PW
3473
-
-
45
Fire mode setting
Fire Mode Sel
0: None
0
None
-
1
Fire Mode
2
Test Mode
46
Fire mode run
direction
Fire Mode Dir
0: Forward
0
Forward
-
1
Reverse
47
Fire mode run
frequency
Fire Mode Freq
60.00
0–max Freq
Hz
48
Fire mode
operation count
Fire Mode Cnt
0
-
-
IN
6575
Digital input
configuration
Px Define
40: Fire
Mode
0-55
-