EasyManua.ls Logo

LSIS LSLV0055H100-4COFN - Control Function Group (CON)

LSIS LSLV0055H100-4COFN
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table of Functions
423
8.4 Control Function Group (CON)
Data in the following table will be displayed only when the related code has been selected.
*O: Write-enabled during operation, Δ: Write-enabled when operation stops, X: Write-
disabled
Cod
e
Comm.
Addres
s
Name
LCD Display
Setting Range
Initial
Value
Property*
Ref.
00
-
Jump Code
Jump Code
1-99
4
O
p.65
04
0h1404
Carrier
frequency
Carrier Freq
1.0- 15.0
(kHz)
3.0
O
p.242
05
0h1405
Switching
mode
PWM Mode
0
Normal
PWM
0:
Normal
PWM
Δ
p.242
1
Low
leakage
PWM
13
0h140
D
Anti-hunting
regulator
mode
AHR Sel
0
No
1 : Yes
Δ
p.232
1
Yes
14
0h140
E
Anti-hunting
regulator P-
Gain
AHR P-Gain
0-32767
1000
O
p.232
15
0h140F
Anti-hunting
regulator
start
frequency
AHR Low
Freq
0.00-AHR
High Freq
0.50
O
p.232
16
0h1410
Anti-hunting
regulator end
frequency
AHR High
Freq
AHR Low
Freq-400.00
400.00
O
p.232
17
0h1411
Anti-hunting
regulator
compensatio
n voltage limit
rate
AHR limit
0-20
2
O
p.232
21
26
0h1415
Auto torque
boost filter
ATB Filt
Gain
1 9999
(msec)
10
O
p.125
26
CON-2122 are displayed when DRV-15 is set to Auto 2‘.