Learning Basic Features
128
4.16 Start Mode Setting
Select the start mode to use when the operation command is input with the motor in the
stopped condition.
4.16.1 Acceleration Start
Acceleration start is a general acceleration mode. If there are no extra settings applied, the
motor accelerates directly to the frequency reference when the command is input.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
ADV
07
Start mode
Start mode
0
Acc
0–1
-
4.16.2 Start After DC Braking
This start mode supplies a DC voltage for a set amount of time to provide DC braking
before an inverter starts to accelerate a motor. If the motor continues to rotate due to its
inertia, DC braking will stop the motor, allowing the motor to accelerate from a stopped
condition. DC braking can also be used with a mechanical brake connected to a motor shaft
when a constant torque load is applied, if a constant torque is required after the the
mechanical brake is released.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
ADV
07
Start mode
Start Mode
1
DC-Start
0–1
-
12
Start DC braking
time
DC-Start
Time
0.00
0.00–60.00
sec
13
DC Injection
Level
DC Inj Level
50
0200
%