Learning Basic Features
4.19 2
nd
Operation Mode Setting
Apply two types of operation modes and switch between them as required. For both the first
and second command source, set the frequency after shifting operation commands to the
multi-function input terminal. Mode swiching can be used to stop remote control during an
operation using the communication option and to switch operation mode to operate via the
local panel, or to operate the inverter from another remote control location.
Select one of the multi-function terminals from codes IN-65–71 and set the parameter value
to 15 (2nd Source).
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV
06
Command source
Cmd Source
1
Fx/Rx-1
0–5
-
07
Frequency
reference source
Freq Ref Src
2
V1
011
-
BAS
04
2nd Command
source
Cmd 2nd Src
0
Keypad
0–5
-
05
2nd Frequency
reference source
Freq 2nd Src
0
KeyPad-1
011
-
IN
65
71
Px terminal
configuration
Px Define
(Px: P1–P7)
17
2nd Source
0–55
-
2nd Operation Mode Setting Details
Code
Description
BAS-04 Cmd 2nd
Src
BAS-05 Freq 2nd
If signals are provided to the multi-function terminal set as the 2
nd
command source (2nd Source), the operation can be performed using
the set values from BAS-04-05 instead of the set values from the DRV-