Learning Basic Features
4.6.2 Terminal Block as a Command Input Device (Fwd/Rev run
commands)
Multi-function terminals can be selected as a command input device. This is configured by
setting DRV-06 (command source) in the Drive group to1 (Fx/Rx)‘. Select 2 terminals for
the forward and reverse operations, and then set the relevant codes (2 of the 7 multi-
function terminal codes, IN-65–71 for P1P7) to 1 (Fx)‘ and 2 (Rx) respectively. This
application enables both terminals to be turned on or off at the same time, constituting a
stop command that will cause the inverter to stop operation.
Grou
p
Code
Name
LCD Display
Parameter Setting
Setting Range
Uni
t
IN
02
Operation
direction for
Keypad
Keypad Run
Dir
0
Reverse
0–1
-
1
Forward
DRV
06
Command source
Cmd Source
1
Fx/Rx-1
0–5
-
IN
6571
Px terminal
configuration
Px Define(Px:
P1 P7)
1
Fx
055
-
2
Rx
Fwd/Rev Command by Multi-function Terminal Setting Details
Code
Description
DRV-06Cmd
Source
Set to 1 (Fx/Rx-1).
IN-65–71 Px
Define
Assign a terminal for forward (Fx) operation.
Assign a terminal for reverse (Rx) operation.