Learning Advanced Features
192
Note
The lubrication function can be used to delay inverter operations, depending on the working
environment, since the inverter waits for the time set at AP2-46 (Lub Op Time) each time a
run command is received.
Lubrication operation is one of the essential system features that are available in both
HAND and AUTO modes.
5.12 Flow Compensation
In a system with a pipeline, longer pipes and higher flow rate cause greater pressure loss. A
flow compensation operation can compensate for pressure loss by increasing the volume of
the PID reference.
Grou
p
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
AP1
30
Flow Comp
function options
Flow Comp
Sel
-
0
No
-
1
Yes
31
Max Comp
amount
Max Comp
Value
-
0–Unit Band
-
Flow Compensation Setting Details
Code
Description
AP1-30
Flow Comp
Sel
Sets the Flow Compensation function options.
AP1-31 Max
Comp Value
Sets the maximum compensation volume. This function is based on a PID
operation. The volume is given the same unit used for the PID reference.