5.48.2 Fault Trip Output using Multi-function Output Terminal and Relay
The inverter can output a fault trip state using the multi-function output terminal (Q1) and
relay (Relay 1).
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
OUT
30
Fault trip output mode
Trip Out Mode
010
-
bit
31
Multi-function relay 1
Relay 1
23
Trip
-
-
32
Multi-function relay 2
Relay 2
14
Run
-
-
33
Multi-function relay 3
Relay 3
0
none
-
34
Multi-function relay 4
Relay 4
0
none
-
35
Multi-function relay 5
Relay 5
0
none
-
36
Multi-function output1
Q1 Define
0
none
-
-
53
Fault trip output on
delay
TripOut OnDly
0.00
0.00–100.00
sec
54
Fault trip output off
delay
TripOut OffDly
0.00
0.00–100.00
sec
Fault Trip Output by Multi-function Output Terminal and Relay - Setting Details
Code
Description
OUT-30 Trip Out
Mode
Fault trip relay operates based on the fault trip output settings.
Item
bit on
bit off
Keypad
display
Select a fault trip output terminal/relay and select 29‘ (Trip Mode) at
codes OUT- 3133. When a fault trip occurs in the inverter, the relevant
terminal and relay will operate. Depending on the fault trip type, terminal
and relay operation can be configured as shown in the table below.
Setting
Function
bit3
bit2
bit1
Operates when low voltage fault trips occur
Operates when fault trips other than low
voltage occur
Operates when auto restart fails (PRT-08
09)