309
Learning Advanced Features
Code
Description
31
PumpClean
Sel
Outputs a signal when a pump cleaning function is in
operation.
32
LDT Trip
Outputs a signal when an LDT trip occurs.
33
Damper
Control
Outputs a signal when a damper open signal is set at
IN-6571 multi-function terminals and run command is
on.
34
CAP.Warnin
g
Outputs a signal when value of the PRT-85 is lower
than the value of the PRT-86 (CAP life cycle
examination do not operate properly).
35
Fan
Exchange
Outputs a signal when fan needs to be replaced.
36
AUTO State
Outputs a signal in AUTO mode.
37
HAND
State
Outputs a signal in HAND mode.
38
TO
Outputs a signal at pulse output.
39
Except Date
Outputs a signal when operating the exception day
schedule.
40
KEB
Operating
Outputs a signal at KEB operation.
41
BrokenBelt
Outputs a signal when a Broken belt is in operation.
OUT-36 Q1
Define
Select an output item for the multi-function output terminal (Q1) of the terminal
block. Q1 stands for the open collector TR output.
OUT-41
DO State
Used to check On/Off state of the D0 by each bit.
FDT-1 and FDT-2 functions are related to the frequency setting of the inverter. If the inverter
enters standby mode by pressing the off key during auto mode operation, FDT-1 and FDT-2
function operation may be different because the set frequency of the inverter is different
compared to the set frequency of the auto mode.
If monitoring signals such as Under load‘ or‘ LDT‘ are configured at multi-function output
terminals, signal outpouts are maintained unless certain conditions defined for signal cutoff
are met.