Learning Advanced Features
5.7 Slip Compensation Operation
Slip refers to the variation between the setting frequency (synchronous speed) and motor
rotation speed. As the load increases there can be variations between the setting frequency
and motor rotation speed. Slip compensation is used for loads that require compensation of
these speed variations.
Slip Compensation Operation Setting Details
Set DRV-09 to ‗2 (Slip Compen)‘ to carry out the slip compensation
operation.
Set the capacity of the motor connected to the inverter.
Enter the number of poles from the motor rating plate.
Enter the number of rated rotations from the motor rating plate.
= Rated slip frequency
= Rated frequency
= Number of the rated motor rotations