RS-485 Communication Features
7.3.6 LS INV 485 Protocol
The slave device (inverter) responds to read and write requests from the master device
(PLC or PC).
Request
Normal Response
Error Response
• A request starts with ENQ and ends with EOT.
• A normal response starts with ACK and ends with EOT.
• An error response starts with NAK and ends with EOT.
• A station ID indicates the inverter number and is displayed as a two-byte ASCII-HEX
string that uses characters 0-9 and A-F.
• CMD: Uses uppercase characters (returns an IF error if lowercase characters are
encountered)—please refer to the following table.
Request monitor registration
Perform monitor registration