315
Learning Advanced Features
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
72
Inverter operation
accumulated time
initialization
Time Reset
0
No
0–1
-
74
Cooling fan operation
accumulated time
Fan time
0/00/00 00:
00
-
min
75
Cooling fan operation
accumulated time
initialization
Fan Time
Reset
0
No
0–1
-
Operation Time Monitor Setting Details
Code
Description
CNF-70 On-time
Displays accumulated power supply time. Information is displayed in
[YY/MM/DD Hr: Min (0/00/00 00: 00)] format.
CNF-71 Run-
time
Displays accumulated time of voltage output by operation command input.
Information is displayed in [YY/MM/DD Hr: Min (0/00/00 00: 00)] format.
CNF-72 Time
Reset
Setting 1 (Yes) will delete the power supply accumulated time (On-time)
and operation accumulated time (Run-time) and is displayed as 0/00/00 00:
00 format.
CNF-74 Fan time
Displays accumulated time of the inverter cooling fan operation. Information
will be displayed in [YY/MM/DD Hr: Min (0/00/00 00: 00)] format.
CNF-75
Fan Time Reset
Setting 1 (Yes) will delete the cooling fan operation accumulated time (on-
time) and operation accumulated time (Run-time) and will display it in
0/00/00 00: 00 format.
5.51 PowerOn Resume Using the Serial
Communication
If there is a run command when recovering the power after instantaneous power
interruption using serial communication (Serial Communication [BAC net, LonWorks,
Modbus RTU]), the inverter carries out the run command which was set before the
instantaneous power interruption.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit