335
Learning Protection Features
Low Battery Voltage Warning Detail Settings
Code
Description
PRT-90 Low
Battery
The low battery voltage warning for RTC function installed in the inverter
can be enabled or disabled. The low battery voltage warning occurs when
the battery voltage is lower than 2 V.
Be careful when replacing the battery. Remaining voltage in the battery may cause electric
shock.
Make sure that the battery doesnt fall inside of the inverter.
6.3 Under load Fault Trip and Warning
The following table lists the under load fault trip and warning features of the H100 series
inverter.
Group
Code
Name
LCD Display
Parameter Setting
Setting range
Unit
PRT
23
Under load
detection
Source
UL Source
0
Output
Current
0–1
-
24
Under load
detection Band
UL Band
10.0
0.0100.0
%
25
Under load
warning
selection
UL Warn
Sel
1
Yes
0–1
-
26
Under load
warning time
UL Warn
Time
10.0
0–600.0
sec
27
Under load trip
selection
UL Trip Sel
1
Free-Run
-
-
28
Under load trip
timer
UL Trip
Time
30.0
0–600.0
sec

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS LSLV0055H100-4COFN and is the answer not in the manual?

LSIS LSLV0055H100-4COFN Specifications

General IconGeneral
BrandLSIS
ModelLSLV0055H100-4COFN
CategoryInverter
LanguageEnglish

Related product manuals