Learning Basic Features
98
4.2.6 Setting a Frequency Reference via RS-485 Communication
Control the inverter with upper-level controllers, such as PCs or PLCs, via RS-485
communication. Set the Frq (Frequency reference source) code (code 07) in the DRV
group to 6 (Int 485) and use the RS-485 signal input terminals (S+/S-/SG) for
communication. Refer to 7 RS-485 Communication features on page 349.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV
07
Frequency reference
source
Freq Ref
Src
6
Int 485
011
-
COM
01
Integrated RS-485
communication
inverter ID
Int485 St ID
-
1
1
MaxComID*
-
02
Integrated
communication
protocol
Int485
Proto
0
ModBus
RTU
0–6
-
2
LS Inv 485
4
BACnet
5
Metasys-N2
6**
Modbus
Master
03
Integrated
communication speed
Int485
BaudR
3
9600 bps
0–8
-
04
Integrated
communication frame
configuration
Int485
Mode
0
D8/PN/S1
0–3
-
1
D8/PN/S2
2
D8/PE/S1
3
D8/PO/S1
*If AP1-40 is set to 4(Serve Drv), MaxComID is8, and if COM-02 is set to4(BACnet),
MaxComID is 127‘. Otherwise MaxComID is250‘.
** COM-02 is automatically set to 6(Modbus Master)‘ when AP1-40 is set to2 or 3‘.
Otherwise a user can set the parameter value at user‘s choice.