Learning Protection Features
6.3.7 No Motor Trip
If an operation command is run when the motor is disconnected from the inverter output
terminal, a ‗no motor trip‘ occurs and a protective operation is performed by the system.
Operation for no motor
trip
No motor trip current level
No Motor Trip Setting Details
PRT-32 No Motor
Level,
PRT-33 No Motor Time
If the output current value [based on the rated current (BAS-13)] is
lower than the value set at PRT-32 (No Motor Level), and if this
continues for the time set at PRT-33 (No Motor Time), a ‗no motor
trip‘ occurs.
If BAS-07 (V/F Pattern) is set to ‗1 (Square)‘, set PRT-32 (No Motor Level) to a value lower than
the factory default. Otherwise, a ‗no motor trip,‘ due to a lack of output current, will occur when
the ‗no motor trip‘ operation is set.
6.3.8 Broken Belt
It is a function to detect a problem in case that a Belt or Coupling is broken while a pump is
used.
Function frequency of
broken belt