• Wherever possible use cables with the largest cross-sectional area for mains power wiring,
to ensure that voltage drop does not exceed 2%.
• Use copper cables rated for 600 V, 75 ℃ for power terminal wiring.
• Use copper cables rated for 300 V, 75 ℃ for control terminal wiring.
• The inverters in the range between 15 and 90 kW must be grounded conveniently with
fixed connections.
• The inverters in the range between 5,5kW and 11kW must be grounded with and
industrial connector according to IEC 60309.
• The minimum size of the protective earthing conductor shall comply with the local safety
regulations for high protective earthing conductor current equipment.
• Only one conductor per terminal should be simultaneously connected