Learning to Perform Basic Operations
User & Macro mode and Trip mode are not displayed when all the inverter settings are set
to the factory default (User & Macro mode must be configured before it is displayed on the
keypad, and Trip mode is displayed only when the inverter is at fault, or has previous trip
fault history).
3.2.2 Operation Modes
The inverter is operable only when it is in HAND or AUTO mode. HAND mode is for local
control using the keypad, while AUTO mode is for remote control via communication. On
the other hand, the inverter stops operating when it is in OFF mode. Select one of the
modes (HAND / AUTO / OFF) to operate the inverter or stop the operation.
Follow the examples below to learn how to switch between operation modes.
Operating the Inverter in HAND mode
1 Turn on the inverter. The inverter enters OFF mode and the OFF LED turns on.
2 Move to Parameter mode and set DRV-07 (frequency reference) to ā0 (keypad)ā.
3 Press the [HAND] key to enter HAND mode (local control mode). HAND mode LED
turns on (the OFF LED turns off) and the inverter begins to operate.
4 Press the [OFF] key to stop the inverter operation. The inverter stops operating and the
OFF LED turns on.