Learning Advanced Features
when the inverter starts (it is different from DRV-03 acceleration gradient).
Refers to the time it takes to reach the 0 step (stop) from the minimum
pump operation frequency for a Start & End Ramp operation (Freq Limit
Lo) set at ADV-25 (it is different from DRV-03 deceleration gradient).
< Start&End Ramp Adjustment>
In the figure above, AP2-41 defines the acceleration time to the minimum operation
frequency ADV-25 (Freq Limt Lo). AP2-42 defines the deceleration time from the minimum
operation frequency to a stopped state. Time A (normal acceleration time set at DRV-03)
and Time B (normal deceleration time set at DRV-04) in the figure will change according to
the Acc/Dec gradients defined by AP2-41 and AP2-42.
5.16 Decelerating Valve Ramping
This function is used to prevent pump damage due to abrupt deceleration. When the pump
operation frequency reaches the valve ramp frequency (AP2-38 Dec Valve Freq) while
decelerating rapidly based on the deceleration ramp time (set at AP2-42), it begins to slow
down the deceleration based on the deceleration valve ramp time (set at AP2-39 DecValve
Time). Decelerating valve ramp operates when ADV-24 (Freq Limit) is set to ‗1 (Yes)‘.
Dec valve
ramping start
frequency