Learning Protection Features
318
Code
Description
PRT-41 Motor
Cooling
Select the drive mode of the cooling fan, attached to the motor.
Setting
Function
0
Self-cool
As the cooling fan is connected to the motor axis, the
cooling effect varies based on motor speed. Most
universal induction motors have this design.
1
Forced-cool
Additional power is supplied to operate the cooling fan.
This provides extended operation at low speeds.
Motors designed for inverters typically have this
design.
PRT-42 ETH 1 min
The amount of input current that can be continuously supplied to the
motor for 1 minute, based on the motor-rated current (BAS-13).
PRT-43 ETH Cont
Sets the amount of current with the ETH function activated. The range
below details the set values that can be used during continuous operation
without the protection function.