Learning Advanced Features
258
Config Mode Parameter Setting Details
Code
Description
CNF-2 LCD Contrast
Adjusts LCD brightness/contrast on the keypad.
CNF-10 Inv S/W Ver,
CNF-11 Keypad S/W
Ver
Checks the OS version in the inverter and on the keypad.
CNF-12 KPD Title Ver
Checks the title version on the keypad.
CNF-30–32 Option-x
Type
Checks the type of option board installed in the option slot.
The H100 inverters use type-1 option boards only (CNF-30 Option-1
Type). CNF-31 and CNF-32 are not used.
CNF-44 Erase All Trip
Deletes the stored trip history.
CNF-60 Add Title Up
When inverter SW version is updated and more code is added,
CNF-60 settings will add, display, and operate the added codes. Set
CNF-60 to 1 (Yes) and disconnect the keypad from the inverter.
Reconnecting the keypad to the inverter updates titles.
CNF-62 WH Count
Reset
Initialize the accumulated electric energy consumption count.
5.42 Macro Selection
The Macro selection function is used to put various application functions together in a group.
For applications with the H100 series inverters, 7 basic Macro configurations are currently
available. Macro functions cannot be added by the user, but the data can be modified.
Group
Code
Name
LCD Display
Parameter Setting
Setting
Range
Unit
CNF
43
Macro selection
Macro Select
0
Basic
0–7
-
1
Compressor
2
Supply Fan
3
Exhaust
Fan
4
Cooling
Tower
5
Circul.

Table of Contents