235
Learning Advanced Features
If damper or lubrication operations are set for the inverter, Fire mode operation is performed
after the delay times set in the relevant operations.
Note that Fire mode operation voids the product warranty.
In Fire mode test mode, the inverter does not ignore the fault trips or perform a reset restart.
All the fault trips will be processed normally. Fire mode test mode does not increase the Fire
mode count (PRT-48).
When the Fire mode operation is complete, the inverter stops operating and is turned off.
5.26 Energy Saving Operation
5.26.1 Manual Energy Saving Operation
If the inverter output current is lower than the current set at BAS-14 (Noload Curr), the
output voltage must be reduced as low as the level set at ADV-51 (Energy Save). The
voltage before the energy saving operation starts will become the base value of the
percentage. Manual energy saving operation will not be carried out during acceleration and
deceleration.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
ADV
50
Energy saving
operation
E-Save
Mode
1
Manual
0
None
-
1
Manual
2
Auto
51
Energy saving
amount
Energy
Save
30
030
%
5.26.2 Automatic Energy Saving Operation