Learning Advanced Features
234
Grou
p
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
OUT
3135
Digital output
configuration
Relay1-5
27: Fire
Mode
0-41
-
36
TR output
configuration
Q1 define
27: Fire
Mode
0-41
-
When the multi-function terminal configured for Fire mode is turned on, the inverter ignores
all other commands and operates in the direction set at PRT-46 (Fire mode run direction) at
the speed set at PRT-47 (Fire mode run frequency). In Fire mode, the inverter ignores any
faults, other thanASHT,‘ Over Current 1,‘Over Voltage,Ground F, and continues to
operate. If any of the faults that can stop inverter operation occur, the inverter automatically
performs a reset restart to continue the operation.
Fire Mode Function Setting Details
Code
Description
PRT-44 Fire
Mode PW
Fire mode password is 3473.
A password must be created to enable Fire mode. PRT-45 (Fire Mode Sel)
can be modified only after the password is entered.
PRT-45 Fire
Mode Sel
Sets the Fire Mode.
Setting
Function
0
None
Fire mode is not used.
1
Fire Mode
Normal Fire mode
2
Test Mode
Fire mode test mode
In Fire test mode, faults are normally processed.
Using Fire test mode does not increase the count
value at PRT-48 (Fire Mode Cnt).
PRT-46 Fire
Mode Dir
Sets the run direction for Fire mode operation.
PRT-47 Fire
Mode Freq
Sets the operation frequency for Fire mode.
PRT-48 Fire
Mode Cnt
Counts the number of the Fire mode operations. The number increases
only when PRT-45 (Fire Mode Sel) is set to Fire Mode‘. The count
increases up to 99, then it does not increase any more.