The Actual Acc/Dec time during an S-curve application
Actual acceleration time = user-configured acceleration time + user-configured acceleration
time x starting gradient level/2 + user-configured acceleration time x ending gradient level/2.
Actual deceleration time = user-configured deceleration time + user-configured deceleration
time x starting gradient level/2 + user-configured deceleration time x ending gradient level/2.
Note that actual Acc/Dec times become greater than user defined Acc/Dec times when S-curve
Acc/Dec patterns are in use.
4.12 Stopping the Acc/Dec Operation
Configure the multi-function input terminals to stop acceleration or deceleration and operate
the inverter at a fixed frequency.