249
Learning Advanced Features
Set Inverter input power voltage. Low voltage fault trip level changes automatically to the
set voltage standard.
Group
Code
Name
LCD
Display
Parameter Setting
Setting Range
Unit
BAS
19
Input power voltage
AC Input
Volt
200
Type
220
170240
V
400
Type
380
320480
5.34 Read, Write, and Save Parameters
Use read, write, and save function parameters on the inverter to copy parameters from the
inverter to the keypad or from the keypad to the inverter.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
CNF
46
Parameter read
Parameter Read
1
Yes
-
-
47
Parameter write
Parameter Write
1
Yes
-
-
48
Parameter save
Parameter Save
1
Yes
-
-
Read, Write, and Save Parameter Setting Details
Code
Description
CNF-46 Parameter
Read
Copies saved parameters from the inverter to the keypad. Saved
parameters on the keypad will be deleted and replaced with the copied
parameters.
CNF-47 Parameter
Write
Copies saved parameters from the keypad to the inverter. Saved
parameters on the inverter will be deleted and replaced with the copied
parameters. If an error occurs during parameter writing, the previously
saved data will be used. If there is no saved data on the Keypad, EEP
Rom Empty will be displayed.
CNF-48 Parameter
Save
As parameters set during communication transmission are saved to
RAM, the setting values will be lost if the power goes off and on. When
setting parameters during communication transmission, select1 (Yes)
at CNF-48 to save the set parameter.