4.18.3 Frequency Jump
Use frequency jump to avoid mechanical resonance frequencies. The inverter will avoid
identified ranges during acceleration and deceleration. Operation frequencies cannot be set
within the pre-set frequency jump band.
When a frequency setting is increased, while the frequency parameter setting value
(voltage, current, RS-485 communication, keypad setting, etc.) is within a jump frequency
band the frequency will be maintained at the lower limit value of the frequency band. Then,
the frequency will increase when the frequency parameter setting exceeds the range of
frequencies used by the frequency jump band.
Group
Code
Name
LCD
Display
Parameter
Setting
Setting Range
Unit
ADV
27
Frequency
jump
Jump Freq
0
0–1
0–1
-
28
Jump
frequency lower
limit1
Jump Lo 1
10.00
0.00–Jump
frequency upper limit
1
Hz
29
Jump
frequency
upper limit1
Jump Hi 1
15.00
Jump frequency
lower limit 1–
Maximum frequency
Hz
30
Jump
frequency lower
limit 2
Jump Lo 2
20.00
0.00–Jump
frequency upper limit
2
Hz
31
Jump
frequency
upper limit 2
Jump Hi 2
25.00
Jump frequency
lower limit 2–
Maximum frequency
Hz
32
Jump
frequency lower
limit 3
Jump Lo 3
30.00
0.00–Jump
frequency upper limit
3
Hz
33
Jump
frequency
upper limit 3
Jump Hi 3
35.00
Jump frequency
lower limit 3–
Maximum frequency
Hz