Learning Protection Features
6.3.5 Trip Status Reset
Restart the inverter, using the keypad or analog input terminal, to reset the trip status.
Px terminal setting
options
Trip Status Reset Setting Details
Press the [Stop/Reset] key on the keypad or use the multi-function input
terminal to restart the inverter. Set the multi-function input terminal to ‗3‘
(RST) and turn on the terminal to reset the trip status.
6.3.6 Operation Mode for Option Card Trip
Option card trips may occur when an option card is used with the inverter. Set the operation
mode for the inverter when a communication error occurs between the option card and the
inverter body, or when the option card is detached during operation.
Operation mode
for option card trip
Operation Mode on Option Trip Setting Details
The inverter output is blocked and fault trip
information is shown on the keypad.
The motor decelerates to the value set at PRT-07
(Trip Dec Time).