Learning Advanced Features
- if ADV-10 (PowerOn Resume) is set to ‗Yes‘, and the terminal input is turned off
instantly after it is turned on (the operation is triggered), and if the inverter is turned
off during a pump clean then is turned back on again, the pump clean operation is
not resumed (because the input terminal is not on when the inverter is turned on).
- if the terminal input is kept on after it is initially turned on, 1 pump clean cycle is
operated.
5.15 Start & End Ramp Operation
This function is used to rapidly accelerate the pump to the normal operating level, or to
rapidly decelerate the pump and stop it. Start & End ramp operation is performed when
ADV-24 (Freq Limit) is set to ‗1 (Yes).‘
Start & End Ramp
Gradient
Start & End Ramp Operation Setting Details
Sets the pump Start & End Ramp options.
The Start & End Ramp operation is not used.
Use the Start & End Ramp operation.
Refers to the time it takes to reach the minimum pump operation
frequency for a Start & End Ramp operation (Freq Limit Lo) set at ADV-25