Preparing the Installation
5
1.3 Installation Considerations
Inverters are composed of various precision, electronic devices, and therefore the
installation environment can significantly impact the lifespan and reliability of the product.
The table below details the ideal operation and installation conditions for the inverter.
Items
Description
Ambient Temperature*
-10 50 (40 and above, 2.5% / Current Derating
search. 50 75% of the rated current of the drive if possible)
Ambient Humidity
90% relative humidity (no condensation)
Storage Temperature
- 4149 F (-2065 )
Environmental Factors
An environment free from corrosive or flammable gases, oil residue
or dust
Altitude/Vibration
Lower than 3,280 ft (1,000 m) above sea level/less than 0.6 G (5.9
m/sec
2
)
Air Pressure
70 106 kPa
* The ambient temperature is the temperature measured at a point 2 (5 cm) from the
surface of the inverter.
Do not allow the ambient temperature to exceed the allowable range while operating the

Table of Contents