4.2.1 Keypad as the Source (KeyPad-1 setting)
You can modify frequency reference by using the keypad and apply changes by pressing
the [ENT/PROG] key. To use the keypad as a frequency reference input source, go to DRV-
07 (Frequency refernce source) and change the parameter value to ‗0 (Keypad-1)‘. Input
the frequency reference for an operation at DRV-01 (Frequency reference).
0.00, Low
Freq– High
Freq*
Frequency
reference
source
* You cannot set a frequency reference that exceeds the Max. Frequency, as configured
with DRV-20.
4.2.2 Keypad as the Source (KeyPad-2 setting)
You can use the [UP] and [DOWN] cursor keys to modify a frequency reference. To use this
as a second option, set the keypad as the source of the frequency reference, by going to
DRV-07 (Frequency reference source) and change the parameter value to ‗1 (Keypad-2)‘.
This allows frequency reference values to be increased or decreased by pressing the [UP]
and [DOWN] cursor keys.
Frequency
reference
source
0.00, Low Freq–
High Freq*
*You cannot set a frequency reference that exceeds the Max. Frequency, as configured
with DRV-20.
4.2.3 V1 Terminal as the Source
You can set and modify a frequency reference by setting voltage inputs when using the V1
terminal. Use voltage inputs ranging from 0–10 V (unipolar) for forward only operation. Use