Learning Protection Features
6.2.5 Dynamic Braking (DB) Resistor Configuration
For H100 series, the braking resistor circuit is integrated inside the inverter.
Braking resistor
configuration
Multi-function
relay 1–5 item
Multi-function
output 1 item
Dynamic Breaking Resistor Setting Details
Set the braking resistor configuration (%ED: Duty cycle). The braking
resistor configuration sets the rate at which the braking resistor operates
for one operation cycle. The maximum time for continuous braking is 15
sec and the braking resistor signal is not output from the inverter after the
15 sec period elapses. An example of braking resistor set up is as follows:
[Example 1]