191
Learning Advanced Features
5.11 Lubrication Operation
During a lubrication operation, the inverter outputs the lubrication signal through one of the
output relays when the inverter receives a run command. The inverter does not start
operating until the time set at AP2-46 (Lub Op Time) has elapsed and the Lubrication signal
is turned off.
Grou
p
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
AP2
46
Lubrication
operation time
Lub Op
Time
0.1600.0
(sec)
OUT
31-35
Multi-function relay
1–5
Relay 1–5
33 (Damper
Control)
-
-
Lubrication Operation Setting Details
Code
Description
AP2-46 Lub Op
Time
Outputs the lubrication signal for a set time when the inverter run
command is turned on. The inverter starts operating when the set time
has elapsed.
OUT-3135 Relay
1–5
Sets one of the output relays (OUT-31–35) to 30 (Lubrication)‘ to
enable the Lubrication function.