4.10.2 Acc/Dec Time Based on Operation Frequency
Acc/Dec times can be set based on the time required to reach the next step frequency from
the existing operation frequency. To set the Acc/Dec time values based on the existing
operation frequency, set BAS-08 (acc/dec reference) in the Basic group to ā1 (Delta Freq)ā.
Acc/Dec Time Based on Operation Frequency ā Setting Details
Set the parameter value to 1 (Delta Freq) to set Acc/Dec times based on
Maximum frequency.
Set the Acc/Dec time based on Maximum
frequency.
Set the Acc/Dec time based on Operation
frequency.
If Acc/Dec times are set to 5 seconds, and multiple frequency references
are used in the operation in 2 steps, at 10 Hz and 30 Hz, each acceleration
stage will take 5 seconds (refer to the graph below).