LSIS LSLV0055H100-4COFN - Configuring Acc;Dec Time Switch Frequency

LSIS LSLV0055H100-4COFN
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Learning Basic Features
114
Code
Description
Acc/Dec time
P7
P6
0
-
-
1
-
2
-
3
[Multi-function terminal P6, P7 configuration]
IN-89 In Check
Time
Set the time for the inverter to check for other terminal block inputs. If
IN-89 is set to 100 ms and a signal is supplied to the P6 terminal, the
inverter searches for other inputs over the next 100 ms. When the time
expires, the Acc/Dec time will be set based on the input received at P6
4.10.4 Configuring Acc/Dec Time Switch Frequency
You can switch between two different sets of Acc/Dec times (Acc/Dec gradients) by
configuring the switch frequency without configuring the multi-function terminals.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
DRV
03
Acceleration time
Acc Time
10.0
0.0600.0
sec
04
Deceleration time
Dec Time
10.0
0.0600.0
sec
BAS
70
Multi-step
acceleration
time1
Acc Time-1
20.0
0.0600.0
sec
71
Multi-step
deceleration
time1
Dec Time-1
20.0
0.0600.0
sec
ADV
60
Acc/Dec time
switch frequency
Xcel Change
Fr
30.00
0–Maximum
frequency
Hz