Learning Advanced Features
In the graph above, Pipe Break occurs if the feedback is smaller than the value caculated
by multiplying the two values set at PID-04 and PRT-61(PID-04 x PRT-61) at the inverter‘s
maximum output (when PID output is the maximum set value, or the inverter is running at
the frequency set at DRV-20).
5.20 Pre-heating Function
This function uses current to heat up the motor or pump to avoid the motor or the pump
freezing when they are not in operation.
Initial heating
output current
Initial heating
output duty
Initial Heating Setting Details
Sets the current to be used for initial heating. Sets the current to motor
no-load current % value.
Sets the duty (time) for the current to be used for initial heating, from 10
seconds to % value.
Sets a certain delay time to prevent from an over current trip that may
occur when a DC input is performed after the inverter Free-Run stop.
Performs the Pre Heat function if the Pre Heat (44) terminal is set.
The initial heating function continually operates when the set multi-function input terminal is
on and until the inverter command is on. If an inverter command is input while the initial
heating function is operating, the inverter starts operation immediately.