209
Learning Advanced Features
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
61
Pipe Break
Detection
variation
PipeBroken
Dev
97.5
0100
%
62
Pipe Break
Detection time
PipeBroken
DT
10.0
0–6000.0
Sec
OUT
31
36
Relay output 15
Relay15
28
Pipe Broken
-
Pipe Break Detection Details
Code
Description
PRT-60
PipeBroken Sel
Select the operation while detecting Pipe Breaks
Setting
Function
0
None
No operation
1
Warning
The inverter displays a warning message.
2
Free-Run
The inverter free-runs, then stops.
3
Dec
The inverter decelerates, then stops.
PRT-61
PipeBroken Dev
Sets the Pipe Break Detection level. Set the detect level by multiplying the
set value for PRT-61 by PID Reference.
PRT-62
PipeBroken DT
Sets the detect delay time. Pipe Break operates if the Pipe Break situation
is maintained for a set amount of time.
OUT31–36
Define
If Pipe Break (28) is set, when a Pipe Break occurs, the inverter sends out
output with Relay.