107
Learning Basic Features
Forward/Reverse Run Prevention Setting Details
Code
Description
ADV-09 Run
Prevent
Choose a direction to prevent.
Setting
Description
0
None
Do not set run prevention.
1
Forward Prev
Set forward run prevention.
2
Reverse Prev
Set reverse run prevention.
4.8 Power-on Run
A power-on run feature can be setup to start an inverter operation after powering up based
on the run commands by terminal inputs or communication (if they are configured). In
AUTO mode, the inverter starts operating at power-on when the following conditions are
met.
Terminal block input as the command source
(If they have been configured). To enable power-on run, set DRV-06 (command source) to
1 (Fx/Rx-1) or2 (Fx/Rx-2) in the Drive group and ADV-10 to1 in the Advanced group.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV
06
Command
source
Cmd Source
1, 2
Fx/Rx-1 or
Fx/Rx-2
0–5
-
ADV
10
Power-on run
Power-on
Run
1
Yes
0–1
-