Restarting the inverter will activate Easy Start On. Set the
values in the following screens on the Keypad. To escape from
Easy Start On, press the [ESC] key.
Start Easy Set: Select ‗Yes‘.
CNF-99: Select a macro.
BAS-10 60/50 Hz Sel: Set motor rated frequency.
DRV-14 Motor Capacity: Set motor capacity.
BAS-13 Rated Curr: Set motor rated current.
BAS-15 Rated Volt: Set motor rated voltage.
BAS-11 Pole Number: Set motor pole number.
BAS-19 AC Input Volt: Set input voltage.
PRT-08 Reset Restart: Sets the restart voltage when
performing a trip reset.
PRT-09 Retry Number: Sets the number of restart trial when
performing a trip reset.
COM-96 PowerOn Resume: Sets the serial communication
restart function.
CON-71 SpeedSearch: Set SpeedSearch.
DRV-06 Cmd Source: Set command source.
DRV-07 Freq Ref Src: Set Frequency Reference source.
When the settings are complete, the minimum parameter