Learning Advanced Features
256
5.40 Easy Start On
Run Easy Start On to easily setup the basic motor parameters required to operate a motor
in a batch. Set CNF-61 (Easy Start On) to1 (Yes)‘ to activate the feature, initialize all
parameters by setting CNF-40 (Parameter Init) to1 (All Grp)‘, and restart the inverter to
activate Easy Start On.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
CNF
61
Parameter easy start
settings
Easy Start On
1
Yes
-
-
Easy Start On Setting Details
Code
Description
CNF-61 Easy Start
On
Follow the procedures listed below to set the easy start on parameters.
No
Procedures
1
Set CNF-61 (Easy Start On) to1(Yes)‘.
2
Select1 (All Grp) in CNF-40 (Parameter Init) to initialize all
parameters in the inverter.
3
Restarting the inverter will activate Easy Start On. Set the
values in the following screens on the Keypad. To escape from
Easy Start On, press the [ESC] key.
Start Easy Set: Select Yes‘.
CNF-99: Select a macro.
BAS-10 60/50 Hz Sel: Set motor rated frequency.
DRV-14 Motor Capacity: Set motor capacity.
BAS-13 Rated Curr: Set motor rated current.
BAS-15 Rated Volt: Set motor rated voltage.
BAS-11 Pole Number: Set motor pole number.
BAS-19 AC Input Volt: Set input voltage.
PRT-08 Reset Restart: Sets the restart voltage when
performing a trip reset.
PRT-09 Retry Number: Sets the number of restart trial when
performing a trip reset.
COM-96 PowerOn Resume: Sets the serial communication
restart function.
CON-71 SpeedSearch: Set SpeedSearch.
DRV-06 Cmd Source: Set command source.
DRV-07 Freq Ref Src: Set Frequency Reference source.
When the settings are complete, the minimum parameter