Learning Protection Features
To receive PTC signal at V1 input terminal, set PRT-35 (Thermal InSrc) to0 (Thermal In)‘
and set the Analog1 input selection switch (SW3) to T1.
To receive PTC signal at I2 input terminal, set PRT-35 (Thermal InSrc) to 1 (V2)‘ and set
SW 4 (Analog2 input selection switch) to V2. The sensor does not operate if SW4 is set to
I2.
When the inverter detects a motor overheat, motor overheat trip occurs with internal delay
time. The trip delay time is not reset instantly when the trip condition is released, but it only
decreases as time passes.
6.1.3 Overload Early Warning and Trip
A warning or fault trip (cutoff) occurs when the motor reaches an overload state, based on
the motor‘s rated current. The amount of current for warnings and trips can be set
separately.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
range
Unit
PRT
17
Overload warning
selection
OL Warn
Select
1
Yes
0–1
-
18
Overload warning level
OL Warn Level
110
30150
%
19
Overload warning time
OL Warn Time
10.0
030
sec
20
Motion at overload trip
OL Trip Select
1
Free-Run
-
-
21
Overload trip level
OL Trip Level
120
30150
%
22
Overload trip time
OL Trip Time
60.0
0–60.0
sec
OUT
31
35
Multi-function relay 15
item
Relay 1–5
5
Over
Load
-
-