Learning Advanced Features
272
5.44.2 Standby Motor
In case that the number set to MMC in [Relay 1~5] of OUT group is lower than the number of [Num
of Aux], auxiliary motor becomes Standby motor state as much as the difference.
.
Ex) In case that Replay1, 2, 3 and 4, and 5 are set to MMC and the number of [Num of Aux] is 3.
Relay1
Relay2
Relay3
Relay4
Relay5
Operable
Operable
Operable
Standby
Standby
In this case, though only Relay1, 2, 3 operate MMC function and the output of Relay is set to MMC, it
doesnt work as long as the order is not changed by Interlock and Auto Change.