Learning Protection Features
328
6.2.2 External Trip Signal
Set one of the multi-function input terminals to 4 (External Trip) to allow the inverter to stop
operation when abnormal operating conditions arise.
Group
Code
Name
LCD Display
Parameter Setting
Setting
range
Unit
IN
65–
71
Px terminal setting
options
Px Define(Px: P1–
P7)
4
External Trip
0-55
-
87
Multi-function input
contact selection
DI NC/NO Sel
-
bit
External Trip Signal Setting Details
Code
Description
IN-87 DI NC/NO
Sel
Selects the type of input contact. If the mark of the switch is at the bottom
(0), it operates as an A contact (Normally Open). If the mark is at the top (1),
it operates as a B contact (Normally Closed).
The corresponding terminals for each bit are as follows:
Bit
7
6
5
4
3
2
1
Terminal
P7
P6
P5
P4
P3
P2
P1