Learning Advanced Features
302
Code
Description
100%).
OUT-06 AO1
Monitor
Monitors the analog output value. Displays the maximum output voltage as
a percentage (%) with 10 V as the standard.
5.47.2 Analog Pulse Output
Output item selection and pulse size adjustment can be made for the TO (Pulse Output)
terminal.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
OUT
61
Pulse output setting
TO Mode
0
Frequency
015
-
62
Pulse output gain
TO Gain
100.0
-1000.0
1000.0
-
63
Pulse output bias
TO Bias
1000.0
-100.0100.0
-
64
Pulse output filter
TO Filter
5
010000
-
65
Pulse output constant
output2
TO Const %
0.0
0.0100.0
%
66
Pulse output monitor
TO Monitor
0.0
0–1000.0
%
Analog Pulse Output Setting Details
Code
Description
OUT-62 TO
Gain, OUT-63
TO Bias
Adjusts output value and offset. If frequency is selected as an output, it will
operate as shown below.



 
The following graph illustrates that the pulse output (TO) changes depend
on OUT-62 (TO Gain) and OUT-63 (TO Bias) values. The Y-axis is an
analog output current (0–32 kHz), and X-axis is a % value of the output
item.
For example, if the maximum frequency set at DRV-20 (Max Freq) is 60 Hz
and present output frequency is 30 Hz, then the x-axis value on the next
graph is 50%.