203
Learning Advanced Features
5.17 Load Tuning
Load tuning refers to an operation that detects the load applied to a specific section of the
inverter operation (current and voltage) and creates an ideal load curve for the under load
and pump clean operations. The two set points to define the section are user-definable, and
are set at 50% and 85% of the base frequency (DRV-18 Base Freq) by default. The load
tuning result values are saved at codes AP2-2AP2-10. These values are user definable as
well.
The minimum set point for the load tuning begins at 15% of the base frequency (DRV-18
Base Freq), and the maximum set point can be set up to the base frequency. If the
frequency limit is set to 1 (Yes) at ADV-24 (Freq Limit), the range is limited within the
frequencies set at ADV-25 (Freq Limit Lo) and ADV-26 (Freq Limit Hi).
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
AP2
01
Load curve
Tuning
Load Tune
No
0
No
-
1
Yes
02
Load curve Low
Freq
Load Fit
LFreq
30.00
Base Freq*15%
Load Fit HFreq
Hz
03
Current for Low
Freq
Load Fit
LCurr
40.0
0.0200.0
%
04
Power for Low
Freq
Load Fit
LPwr
30.0
0.0200.0
%
08
Load curve High
Freq
Load Fit
HFreq
51.00
Load Fit LFreq
High Freq
Hz
09
Current for High
Freq
Load Fit
HCurr
80.0
0.0200.0
%
10
Power for High
Freq
Load Fit
HPwr
80.0
0.0200.0
%
11
Load current for
frequency
Load Curve
Cur
-
-
%
12
Load power for
frequency
Load Curve
Pwr
-
-
%