Learning Advanced Features
204
Load Tuning Setting Details
Code
Description
AP2-01 Load Tune
The inverter performs an automatic tuning to generate an ideal
system load curve.
Setting
Function
0
None
Load tuning is not used.
1
Load Tune
Start load tuning.
AP2-02 Load Fit LFreq
Defines the first frequency set point for load tuning (user definable).
AP2-03 Load Fit LCurr
AP2-04 Load Fit LPwr
Displays the current and power measured at the frequency set at
AP2-02 as a percentage (%) value, based on motor rated current
and rated power. Values for AP2-03 and AP2-04 are user definable.
AP2-08 Load fit HFreq
Defines the second frequency set point for load tuning (user
definable).
AP2-09 Load Fit HCurr
AP2-10 Load Fit HPwr
Displays the current and power measured at the frequency set at
AP2-08 as a percentage (%) value, based on motor rated current
and rated power. Values for AP2-09 and AP2-10 are user definable.
AP2-11 Load Curve Cur
AP2-12 Load Curve
PWR
Monitors the load curve value set at AP2-1 (Load Tune) based on
the current output frequency.
When a load tuning is performed, the inverter measures for 10 seconds the motor current
and power, at the frequencies set at AP2-02 and AP2-09. The motor current and power
values measured here are used to generate an ideal load curve.