EasyManua.ls Logo

LSIS LSLV0055H100-4COFN - Input Terminal Group (IN)

LSIS LSLV0055H100-4COFN
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table of Functions
426
Cod
e
Comm.
Addres
s
Name
LCD Display
Setting Range
Initial
Value
Property*
Ref.
buffering P-
Gain
82
0h1452
Energy
buffering I
gain
KEB I Gain
1-20000
500
O
p.192
83
0h1453
Energy
buffering
acceleration
time
KEB Acc
Time
0.0-600.0
10.0
O
p.192
8.5 Input Terminal Group (IN)
Data In the following table will be displayed only when the related code has been selected.
*O: Write-enabled during operation, Δ: Write-enabled when operation stops, X: Write-
disabled
Cod
e
Comm.
Addres
s
Name
LCD Display
Setting Range
Initial
Value
Propert
y*
Ref.
00
-
Jump Code
Jump Code
1-99
65
O
p.65
01
0h1501
Frequency at
maximum
analog input
Freq at 100%
Start frequency-
Maximum
frequency (Hz)
Maximu
m
frequenc
y
O
p.85
05
30
0h1505
V1 input
voltage
display
V1 Monitor(V)
0~12.00(V) or
-12.00~12.00 (V)
0.00
X
p.85
06
0h1506
V1 input
polarity
selection
V1 Polarity
0
Unipolar
0:
Unipolar
Δ
p.85
1
Bipolar
07
0h1507
Time constant
of V1 input
filter
V1 Filter
0–10000 (ms)
10
O
p.85
30
IN-05 setting range can be changed according to the IN-06 settings.