299
Learning Advanced Features
5.47 Analog Output
An analog output terminal provides an output of 0–10 V voltage, 420 mA current, or 0–32
kHz pulse.
5.47.1 Voltage and Current Analog Output
An output size can be adjusted by selecting an output option at the AO (Analog Output)
terminal. Set the analog voltage/current output terminal setting switch (SW5) to change the
output type (voltage/current).
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
OUT
01
Analog output1
AO1 Mode
0
Frequency
015
-
02
Analog output1 gain
AO1 Gain
100.0
-1000.0
1000.0
%
03
Analog output1 bias
AO1 Bias
0.0
-100.0100.0
%
04
Analog output1 filter
AO1 Filter
5
010000
ms
05
Analog constant
output1
AO1
Const %
0.0
0.0100.0
%
Note
Press regeneration prevention does not operate during accelerations or decelerations; it only
operates during constant speed motor operation. When regeneration prevention is activated,
output frequency may change within the range set at ADV-76 (CompFreq Limit).