Learning Advanced Features
Voltage and Current Analog Output Setting Details
Select a constant value for output. The following example for output
voltage setting.
Outputs operation frequency as a standard. 10
V output is made from the frequency set at
DRV-20 (Max Freq).
10 V output is made from 150% of inverter rated
current.
Sets the outputs based on the inverter output
voltage. 10 V output is made from a set voltage
in BAS-15 (Rated V).
If 0 V is set in BAS-15, 200 V/400 V models
output
10 V based on the actual input voltages (240 V
and
480 V respectively).
Outputs inverter DC link voltage as a standard.
Outputs 10 V when the DC link voltage is 410 V
DC for 200 V models, and 820 V DC for 400 V
models.
Monitors output wattage. 150% of rated output
is the maximum display voltage (10 V).
Outputs set frequency as a standard. Outputs
10 V at the maximum frequency (DRV-20).
Outputs frequency calculated with Acc/Dec
function as a standard. May vary with actual
output frequency. Outputs 10 V.
Outputs command value of a PID controller as a
standard. Outputs approximately 6.6 V at 100%.
Outputs feedback volume of a PID controller as
a standard. Outputs approximately 6.6 V at
100%.
Outputs output value of a PID controller as a
standard. Outputs approximately 10 V at 100%.
Outputs OUT-05 (AO1 Const %) value as a
standard.