Learning Advanced Features
300
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
06
Analog output1
monitor
AO1
Monitor
0.0
0.01000.0
%
Voltage and Current Analog Output Setting Details
Code
Description
OUT-01 AO1
Mode
Select a constant value for output. The following example for output
voltage setting.
Setting
Function
0
Frequency
Outputs operation frequency as a standard. 10
V output is made from the frequency set at
DRV-20 (Max Freq).
1
Output
Current
10 V output is made from 150% of inverter rated
current.
2
Output
Voltage
Sets the outputs based on the inverter output
voltage. 10 V output is made from a set voltage
in BAS-15 (Rated V).
If 0 V is set in BAS-15, 200 V/400 V models
output
10 V based on the actual input voltages (240 V
and
480 V respectively).
3
DC Link Volt
Outputs inverter DC link voltage as a standard.
Outputs 10 V when the DC link voltage is 410 V
DC for 200 V models, and 820 V DC for 400 V
models.
4
Output Power
Monitors output wattage. 150% of rated output
is the maximum display voltage (10 V).
7
Target Freq
Outputs set frequency as a standard. Outputs
10 V at the maximum frequency (DRV-20).
8
Ramp Freq
Outputs frequency calculated with Acc/Dec
function as a standard. May vary with actual
output frequency. Outputs 10 V.
9
PID Ref Value
Outputs command value of a PID controller as a
standard. Outputs approximately 6.6 V at 100%.
10
PID Fdk
Value
Outputs feedback volume of a PID controller as
a standard. Outputs approximately 6.6 V at
100%.
11
PID Output
Outputs output value of a PID controller as a
standard. Outputs approximately 10 V at 100%.
12
Constant
Outputs OUT-05 (AO1 Const %) value as a
standard.