Learning Advanced Features
260
Timer Setting Details
Code
Description
IN-65–71 Px Define
Choose one of the multi-function input terminals and change it to a
timer terminal by setting it to 35(Timer In)‘.
OUT-31 Relay 1,
OUT-36 Q1 Define
Set the multi-function output terminal or relay to be used as a timer
to 22 (Timer out)‘.
OUT-55
TimerOn Delay,
OUT-56
TimerOff Delay
Input a signal (On) to the timer terminal to operate a timer output
(Timer out) after the time set at OUT-55 has passed. When the multi-
function input terminal is off, the multi-function output or relay turns off
after the time set at OUT-56.
5.44 Multiple Motor Control (MMC)
The MMC (Multiple Motor Control) function is used to control multiple motors for a pump
system. The main motor connected with the inverter output is controlled by the PID
controller. The auxiliary motors are connected with the supply power and turned on and off
by the relay within the inverter.
Grou
p
Code
Name
LCD Display
Setting
Setting Range
Unit
AP1
40
MMC function
selection
MMC Sel
0: None
0
None
-
1
Single Ctrl
2
Multi
Follower
3
Multi
Master
4
1
Serve Drv
1
AP1-47~87 and AP1-91~98 are not displayed when AP1-40 is set to ‘4(Serve Drv)‘.